Logger Script
 
 
  ELECTRIC LINEAR TYPE VALVE (FRANGED) ¤Ó ELECTRIC LINEAR TYPE VALVE (JIS20K)
 
The valve which controls two positions or the proportion of cold/hot water, steam and air, district heating. The body is manufactured in castiron and the valve stem, seat, valve plug are in stainless steel. The stuffing box prevents leakage via O-ring and Vition

¡á Technical Data
- Operating Pressure : JIS 20 Kgf/§²
- Operating Temp : -25 ~ 200¡É
- Valve curve : Equal percentage or linear
- Leakage rate : ¡Â 0.01% of Kvs value Class IV

¡á
Application
Hot water : max 180¡É
Chilled water : -25¡É max. in closed circuit only water
 
    with following additives
- Hydrazine, Phosphate, for frost protection.
- Glycol, max 50%, for frost protection.
- Saturated steam, superheated steam 6bar,
.. abs/max 180¡É
 
Model DN FLOW Stroke Sv Pvmax Actuator Ps(Kgf/§²)
mm inch Kvs Cv mm AGE-20 AGE-35 AGE-55
AGE-15F 15 1/2" 3 3.5 20 50 16 20 - -
AGE-20F 20 3/4" 5 5.8 20 50 16 20 - -
AGE-25F 25 1" 10 11.7 20 50 16 20 - -
AGE-32F 32 1-1/4" 12 14 20 50 16 20 - -
AGE-40F 40 1-1/2" 25 29 20 50 16 12 - -
AGE-50F 50 2" 31 36 20 50 10 6 - -
AGE-65F 65 1-1/2" 49 57 20 50 6 - 8.5 -
AGE-80F 80 3" 78 91 20 50 4 - 5.5 -
AGE-100F 100 4" 124 144.5 40 50 2.5 - 3.5 -
AGE-125F 125 5" 200 223 40 50 1.75 - - 3.5
AGE-150F 150 6" 300 350 40 50 1 - - 2.5
¡Ø () Option
  Pvmax in Kgf/§² = max. prem, pressure difference across the valve at which the drive can still safely
......................................open and close the valve.
Psmax in Kgf/§² = max. prem, pressure difference across the valve during malfunction at which the
......................................drive can close the valve.